Through Penetration Firestop Systems Details

[« Return to Firestop Systems Home]

UL DetailTrade DetailDescriptionF-RatingProduct(s)
W-L-0012WL0012a.pdf Max. 30" x 15" blank opening 1 or 2-Hr CP 620
W-L-0013WL0013c.pdf Max. 4" threaded steel conduit with plastic or metal bushings 1 or 2-Hr CP 658T
CFS-BL
W-L-0014WL0014b.pdf Max. 24" x 36" blank opening 1 or 2-Hr CP 675T
W-L-0015WL0015a.pdf Max. 24" x 36" blank opening 1 or 2-Hr CP 675T
W-L-0018WL0018c.pdf Max. 4" steel pipe sleeve 1 or 2-Hr CP 658T
CFS-BL
W-L-0019WL0019c.pdf Max. 4" steel pipe sleeve 1 or 2-Hr CP 658T
CFS-BL
W-L-0023WL0023d.pdf Max. 4" blank steel sleeve 1 or 2 Hr CP 658T
CFS-PL
W-L-0030WL0030a.pdf Max. 240 sq. in. blank opening with a max. dimension of 20" (unframed opening) 1 or 2-hr FS-ONE
W-L-0040WL0040a.pdf Max. 2-1/2” dia or 2” x 2” blank 1 or 2 Hr FS-ONE
W-L-0042WL0042a.pdf Blank opening through gypsum wall assembly 1-hour or 2-hour CFS-BL
W-L-0043WL0043a.pdf Blank opening through gypsum wall assembly 1-hour or 2-hour CFS-BL
W-L-1054WL1054r.pdf Max. 30" steel, cast iron, max. 6" copper, conduit or max. 4" EMT pipe (AS = 0" to 2-1/4") 1 or 2-hr FS-ONE
W-L-1056WL1056e.pdf Max. 12" steel, cast iron, max. 4" copper, conduit or EMT pipe in steel sleeve 2-hour FS-ONE
W-L-1058WL1058h.pdf Max. 16" steel, max. 4" copper, in wire mesh sleeve 2-hour FS-ONE
W-L-1095WL1095d.pdf Max. 1" steel, conduit or EMT pipes (one or more) 1 or 2-hr FS-ONE
W-L-1110WL1110c.pdf Max. 12" steel, cast iron, max. 6" copper, conduit or max. 4" EMT in sleeve 4-hour FS-ONE
W-L-1111WL1111b.pdf Max. 12" steel, max. 6" copper, conduit or max. 4" EMT 4-hour FS-ONE
W-L-1148WL1148d.pdf Max. 8" steel or cast iron pipe or max. 4" conduit or EMT (AS = 0" to 3/8") 1 or 2-hr FS-ONE
W-L-1164WL1164c.pdf Max. 6" steel, copper, conduit or max. 4" EMT pipe in steel pipe sleeve 1 or 2-hr FS-ONE
W-L-1165WL1165b.pdf Max. 6" steel, copper, conduit or max. 4" EMT pipe in steel pipe sleeve 4-hour FS-ONE
W-L-1170WL1170d.pdf Max. 6" copper, (sleeved) (AS = 1/2" to 1-3/8") 1 or 2-hr CP 601S
CP 606
FS-ONE
CFS-SILGG
W-L-1175WL1175b.pdf Max. 4" EMT or steel conduit 1 or 2-hr CP 618
W-L-1176WL1176d.pdf Max. 2" EMT or steel conduits (one or more) 1-hour FS-ONE
W-L-1205WL1205e.pdf Max. 8" steel, cast iron, max. 6" conduit, max. 4" copper, EMT or max. 2" flexible steel conduit (sleeved) (one-sided installation, includes shaft wall) 1 or 2-hr FS-ONE
W-L-1206WL1206e.pdf Max. 8" steel, cast iron, max. 6" conduit, max. 4" copper, EMT or max. 2" flexible steel conduit (sleeved) (one-sided installation, includes shaft wall) 1 or 2-hr FS-ONE
W-L-1214WL1214a.pdf Max. 1" flexible steel conduit 1-hour FS-ONE
W-L-1243WL1243d.pdf Max. 2" aluminum or steel flexible conduit 1 or 2-hr FS-ONE
W-L-1247WL1247a.pdf Max. 6" steel, cast iron, steel conduit or max. 3" copper, or max. 4" EMT pipe (one or more) 2-hour CP 637
W-L-1248WL1248a.pdf Max. 6" steel, cast iron, steel conduit or max. 3" copper, or max. 4" EMT pipe (one or more) 1-hour CP 637
W-L-1249WL1249a.pdf Max. 2" Steel Conduit or EMT (Multiple in 30" x 12" opening) 1 or 2-hr CP 620
W-L-1252WL1252c.pdf Max. 4" steel, cast iron, copper, conduit, or EMT (AS = 0" to 7/8") 1,2,3, or 4-hour CP 606
FS-ONE
W-L-1289WL1289b.pdf Max. 4" steel, cast iron, copper, conduit, or EMT pipe 1 or 2-hour CP 620
W-L-1290WL1290c.pdf Max. 4" steel, cast iron, copper, conduit, or EMT 1 or 2-hr CP 606
W-L-1297WL1297d.pdf Max. 30" steel, cast iron, max. 6" copper, steel conduit or max. 4" EMT pipe 1 or 2-hr CP 606
W-L-1304WL1304c.pdf Max. 4" steel, cast iron, conduit, or EMT (AS = 0" to 1/2") 1 or 2-hr CP 606
FS-ONE
W-L-1359WL1359a.pdf Max. 6" cast iron with "No-Hub" Connector 1 or 2-hr FS-ONE
W-L-1360WL1360c.pdf Max. 24" steel, cast iron, max. 6" copper, steel conduit, or max. 4" EMT (AS varies) 1 or 2-hr CP 601S
CFS-SILGG
W-L-1367WL1367b.pdf Max. 8" steel, cast iron, 6" steel conduit, or 4" copper, EMT 1 or 2-hr CP 675T
W-L-1380WL1380b.pdf Max. 8" steel, cast iron, 6" copper, 4" steel conduit or EMT (shaft wall) (AS = 0" to 7/8") 2 Hr FS-ONE
W-L-1389WL1389b.pdf Multiple max. 2" steel, steel conduit, or EMT 1 or 2 Hr CP 606
FS-ONE
W-L-1392WL1392a.pdf Max. 12" steel, cast iron, max. 6" steel conduit or EMT (sleeved) 1 or 2 Hr FS-ONE
W-L-1402WL1402b.pdf Max. 4" steel, cast iron, steel conduit or EMT (one or more) 1 or 2 Hr CFS-SP WB
W-L-1406WL1406b.pdf Max. 8" steel, cast iron, steel conduit, max. 4" copper or EMT (UL Classified U336 or U366 Wall) 2 Hour FS-ONE
W-L-1408WL1408a.pdf Multiple max. 4" steel, steel conduit, or EMT 1 or 2 Hr FS-ONE
W-L-1410WL1410d.pdf Max. 3" steel, steel conduit, copper or EMT (membrane penetration) (AS = 0" to 1") 1 or 2-hr CP 601S
CP 606
CP 618
FS-ONE
CFS-SILGG
W-L-1412WL1412b.pdf Max. 2" steel, cast iron, steel conduit, or EMT running vertically through plane of wall on one side (AS=0" to 3/4") 1-hour FS-ONE
W-L-1440WL1440a.pdf Max. 1" steel conduit or EMT with steel junction box (AS=0" to 1-1/8") 1 or 2-hr FS-ONE
W-L-1441WL1441a.pdf Max. 3" steel, cast iron, steel conduit, or EMT 1 or 2-hr CP 653
W-L-1462WL1462a.pdf Medical gas station outlet 1 or 2-hr CP 617
W-L-1464WL1464a.pdf Max. 1” single or bundled fledxible steel conduits 1 or 2-Hr FS-ONE
W-L-1465WL1465b.pdf Max. 8” steel, cast iron, 6” steel conduit, 4” copper or EMT w/ sheet metal sleeve 1 or 2-Hr CP 606
FS-ONE
W-L-1497WL1497a.pdf Max. 4" aluminum tube (min. 0.125" thick) (closed piping system) (AS = min 3") 1 or 2 Hour CFS-BL
W-L-2045WL2045a.pdf Max. 2” Polypropylene (PP SCH 80, SDR 7.4, or SDR 11) (AS = 0" to 5/8") 1 or 2 Hour CP 643N
W-L-2075WL2075g.pdf Max. 2" ENT (closed system only) 1 or 2-hr FS-ONE
W-L-2078WL2078n.pdf Max. 10" PVC, CPVC, max. 6" ABS, FRPP or max. 4" PVDF (closed or open) 1 or 2-hr CP 643N
CP 644
W-L-2084WL2084e.pdf Max. 6" PVC, CPVC, ABS or FRPP (closed or open) (sleeve optional) 1 or 2-hr CP 643N
W-L-2098WL2098d.pdf Max. 2" PVC or CPVC (closed system only) 1 or 2-hr FS-ONE
W-L-2128WL2128f.pdf Max. 2" PVC or CPVC (closed or open) (sleeve optional) 1 or 2-hr FS-ONE
W-L-2165WL2165d.pdf Max. 2" Fiber Optic Raceway (Innerduct) or ENT pipe 2-hour FS-ONE
W-L-2184WL2184a.pdf Max. 2" PVC or CPVC (closed system only)(sleeved) 4-hour FS-ONE
W-L-2186WL2186d.pdf Max. 1" PEX (closed system only)(sleeved) 1 or 2-hr FS-ONE
W-L-2196WL2196a.pdf Max. 1-1/2" ABS (closed or open) 1-hour FS-ONE
W-L-2197WL2197a.pdf Max. 1" Fiber Optic Raceway (Innerduct) 1-hour FS-ONE
W-L-2217WL2217e.pdf Max. 4" PVC or CPVC (c,v) (shaft wall) (AS=0" to 1/4") 2-hour CP 643N
W-L-2232WL2232c.pdf Max. 2" PVC (closed or open) 2-hour CP 648-E
W-L-2234WL2234c.pdf Max. 2" ABS (closed or open) 1-hour CP 648-E
W-L-2235WL2235d.pdf Max. 2" ABS, PVC, CPVC , FRPP or 1" PEX (closed or open) 1 or 2-hr CP 648-E
CP 648-S
W-L-2236WL2236d.pdf Max. 8" PVC or CPVC (c,v) (AS=0" to 1-3/8") 1 or 2-hr CP 648-E
W-L-2244WL2244d.pdf Max. 2" PVC or CPVC (closed system only) 1 or 2-hr FS-ONE
W-L-2245WL2245c.pdf Max. 6" PVC, CPVC, ABS or FRPP(closed or open) 4-hour CP 643N
W-L-2251WL2251a.pdf Max. 4" PVC or CPVC (closed or open) 1 or 2-hr FS-ONE
W-L-2284WL2284c.pdf Max. 3" PVC or CPVC (closed or open) 1-hour CP 648-E
W-L-2292WL2292c.pdf Max. 4" PVC connecting to 4" Cast Iron (w/No Hub Coupling) (Shaft Wall) (sleeved) 2-hour CP 643N
FS-ONE
W-L-2295WL2295c.pdf Max. 9" PVDF (closed or open) (sleeved) 2-hour CP 648-E
W-L-2315WL2315b.pdf Max. 12" FRP pipe (closed or open) (sleeved) 2-hour CP 648-E
W-L-2330WL2330a.pdf Max. 6" Glass Pipe 1 or 2-hr FS-ONE
W-L-2335WL2335b.pdf Max. 4" PVC, CPVC, or ABS (closed or open) 1 or 2-hr CP 648-E
W-L-2340WL2340b.pdf Max. 4" PVC, CPVC, or ABS (closed or open) (angled through wall) 1 or 2-hr CP 648-E
W-L-2341WL2341b.pdf Max. 12" PVC or CPVC (closed or open) 1 or 2-hr CP 648-E
W-L-2344WL2344b.pdf Max. 4" PVC or CPVC (closed or open) 2-hour CP 648-E
W-L-2377WL2377e.pdf Max. 2" FlowGuard Gold or Blazemaster CPVC (closed) (AS=0" to 1-1/4") 1 or 2 hr FS-ONE
W-L-2406WL2406c.pdf Max. 6" ABS, PVC, or PVC (closed or open) 1 or 2 hr CP 648-S
W-L-2411WL2411c.pdf Max. 4" PVC, ABS, FRPP or CPVC with optional coupling (c,v) (AS=0" to 1/2") 1 or 2 Hr CP 648-E
W-L-2443WL2443a.pdf Max. 2" ENT (closed system only) 3 or 4 hr CP 618
W-L-2444WL2444a.pdf Max. 2" ENT (closed system only) 3 or 4 hr CP 648-E
FS-ONE
W-L-2445WL2445b.pdf Max. 6" cast iron soil stack with 3" PVC or ABS branch lines 1 or 2 hr CP 648-S
W-L-2447WL2447a.pdf Max. 6" PVC, CPVC, or ABS (closed or open) 1,2,3 or 4-hr CP 648-E
W-L-2453WL2453a.pdf Max. 2" PVC or PP (closed or open) 1 or 2 hr CP 648-E
W-L-2466WL2466a.pdf Max. 1-1/2" PVC, PVC, RNC, or max. 1" PEX (closed)(Max qty = 3) 1 or 2 Hr FS-ONE
W-L-2467WL2467a.pdf Max. 4" diameter bundle of max. 1" diameter PEX (closed) 1 or 2 Hr FS-ONE
W-L-2471WL2471b.pdf Max. 3" PVC, ABS, CPVC, or RNC (UL Classified U336 or U366 Wall) 2 Hour CP 648-S
FS-ONE
W-L-2472WL2472b.pdf Max. 2" PVC, CPVC, or RNC (UL Classified U336 or U366 Wall) 2 Hour FS-ONE
W-L-2473WL2473b.pdf Max. 4" PP (closed or open) (AS = 0" to 1/2") 1 or 2 Hr CP 643N
W-L-2474WL2474c.pdf Max. 2" PVC, CPVC, PEX, RNC (closed or open) 1 or 2 Hr FS-ONE
W-L-2480WL2480a.pdf Max 1" PEX (max qty = 6) (c) (AS=1/2" to 1") 1 or 2-hr FS-ONE
W-L-2482WL2482a.pdf Max 2" PVC (c,v) with optional coupling (AS=0" to 1/2") 1-hour FS-ONE
W-L-2509WL2509a.pdf Max. 2" PP or 50mm Fusiotherm (c,v) (AS=0" to 5/8") 1 or 2-hr CP 643N
W-L-2510WL2510a.pdf Max. 4" PP or 125mm Fusiotherm (c,v) (AS=0" to 1/2") 1 or 2-hr CP 648-E
W-L-2537WL2537a.pdf Max. 1" PEX (bundled) through CP 653 Speed Sleeve 1 or 2-hr CP 606
CP 653
FS-ONE
W-L-2538WL2538a.pdf Max. 2" ENT (one or more) through CP 653 Speed Sleeve 1 or 2-hr CP 606
CP 653
FS-ONE
W-L-2541WL2541a.pdf Max. 3" PVC or CPVC (c,v) through CP 653 Speed Sleeve 1 or 2-hr CP 606
CP 653
FS-ONE
W-L-2546WL2546a.pdf Max. 4" PVC, CPVC, ABS (c,v) max 2" Flowguard Gold, Blazemaster, PVC conduit (nonsymmetrical installation) (AS=0" to 1/2") 1 or 2-hr CP 648-E
W-L-2557WL2557a.pdf Max. 3/8” single or bundled pneumatic tube (max qty = 12) 1 or 2-Hr FS-ONE
W-L-2558WL2558a.pdf Max. ½” Single or bundled Dura-line Mircroduct 1 or 2-hr FS-ONE
W-L-2559WL2559a.pdf Max. ½” Single or bundled Dura-line Mircroduct 1 or 2-hr CP 618
CP 643N
W-L-2567WL2567a.pdf Cable bundle (various cables) in flexible nylon fiber optic cable routing system (sleeved) (AS=0" to 1" outside sleeve) (AS=0" to 3" inside sleeve) 1 or 2-hr CP 618
W-L-2568WL2568a.pdf Cable bundle (various cables) in flexible nylon fiber optic cable routing system (sleeved) (AS=0" to 1" outside sleeve) (AS=0" to 3" inside sleeve) 1 or 2-hr CFS-PL
W-L-2584WL2584a.pdf Max 8" HDPE Plastic Pipe (closed piping system) (AS = min 1-1/4") 1 or 2 Hour CP 648-E
CFS-BL
W-L-3046WL3046e.pdf Cable bundle (power cables)Steel sleeve 1-hour FS-ONE
W-L-3047WL3047d.pdf Cable bundle (power cables) 2-hour FS-ONE
W-L-3058WL3058c.pdf Cable (telephone cable) 2-hour FS-ONE
W-L-3065WL3065z.pdf Cable bundle (various cables) (Steel sleeve optional) (AS=0" to 1") 1 or 2-hr CP 601S
CP 606
CP 618
FS-ONE
W-L-3071WL3071e.pdf Cable bundle (SER power cables) 1 or 2-hr FS-ONE
W-L-3079WL3079d.pdf Cable bundle (various cables)(sleeve optional) 1 or 2-hr FS 657
CFS-BL
W-L-3111WL3111c.pdf Cable bundle (various cables) (sleeve optional) 1 or 2-hr CP 618
W-L-3112WL3112f.pdf Cable bundle (various cables)(sleeved) 1 or 2- hr CP 618
W-L-3122WL3122e.pdf Cable bundle (various cables)(Unique Firestop Sleeve) 1 or 2-hr CP 618
W-L-3139WL3139b.pdf Cable bundle (various cables)(sleeved) 4-hour FS-ONE
W-L-3161WL3161c.pdf Cable bundle (various cables)(sleeved)(shaft wall) 1 or 2-hr FS-ONE
W-L-3185WL3185d.pdf Cable bundle Cable Rack (Telecom) (various Cables) 1 or 2-hr FS 657
CFS-BL
W-L-3213WL3213b.pdf Cable bundle (various cables)(PVC sleeve) 1 or 2-hr CP 618
FS-ONE
W-L-3220WL3220b.pdf Cable bundle (various cables)(Unique Firestop Sleeve) 1 hr CP 618
W-L-3224WL3224c.pdf Cable bundle (various cables) (sleeve optional) 1 or 2-hr CP 658T
CFS-BL
W-L-3226WL3226c.pdf Cable bundle (various cables)(PW Southern steel sleeve) 1 or 2 hr FS 657
CFS-BL
W-L-3272WL3272c.pdf Cable bundle (various cables)(sleeved) 1 or 2 hr CP 658T
CFS-BL
W-L-3273WL3273c.pdf Cable bundle (various cables) (Unique Firestop Sleeve) 3 or 4 hr CP 618
W-L-3277WL3277b.pdf Cable bundle (various cables)(sleeved) 3 or 4 hr CP 658T
CFS-BL
W-L-3278WL3278b.pdf Cable bundle (various cables) (shaft wall) (AS=0" to 1") 2 Hr FS-ONE
W-L-3282WL3282d.pdf Cable bundle (various cables) (Unique Firestop Sleeve) 1 or 2 Hr CFS-PL
W-L-3296WL3296b.pdf Cable bundle (various cables) 1 or 2 Hr CP 675T
FS 657
CFS-BL
W-L-3307WL3307b.pdf Cable bundle (various cables) (UL Classified U336 or U366 Wall) 2-Hour FS-ONE
W-L-3310WL3310a.pdf MC Cables (max qty 3) (membrane penetration) 1 or 2 Hr FS-ONE
W-L-3316WL3316a.pdf Cable bundle (various cables) through Unique Sleeves with "gang plate" 1 or 2-hr CP 618
W-L-3320WL3320c.pdf Max. 3" steel conduit sleeve with various cables inside existing sleeve (membrane penetration) (AS = 0" to 1") 1 or 2-hr CP 601S
CP 606
CP 618
FS-ONE
CFS-SILGG
W-L-3334WL3334e.pdf Blank or cables through CP 653 Speed Sleeve 1 or 2-hr CP 653
W-L-3335WL3335e.pdf Blank or cables through CP 653 Speed Sleeve 1 or 2-hr CP 653
FS-ONE
W-L-3382WL3382a.pdf Cable bundle through gypsum wall assembly (0-12" annular space) 1-hour or 2-hour CFS-BL
W-L-3384WL3384a.pdf Cable Bundle (various cables) through "ganged" Speed Sleeves 1 or 2 Hr CP 653
W-L-3385WL3385a.pdf Cable bundle (various cables) (optional 45º angle) 1,2, or 3-Hr CP 606
FS-ONE
W-L-3391WL3391_111212.pdf Blank or Cables (various) through Firestop Cable Transit 1 or 2 Hour CFS-T
W-L-3392WL3392_022513.pdf Cables (various) through Firestop Cable Transit 1 or 2 Hour CFS-T
W-L-3393WL3393a.pdf Blank or cables through Firestop Retrofit Sleeve Kit 1 or 2 Hr CFS-SL RK
W-L-3394WL3394a.pdf Blank or cables through Firestop Sleeve Kit 1 or 2 Hr CFS-SL SK
W-L-3395WL3395c.pdf Blank or cables through Cable Mangagment Devices using Firestop Gangplate 1 or 2 Hr CP 653
CFS-SL RK
CFS-SL GP
CFS-SL SK
W-L-3396WL3396c.pdf Cable Bundle (various cables) (optional steel pipe sleeve) 1 or 2 Hr CFS-CC
W-L-3414WL3413a.pdf Cable bundle (various cables) (Steel sleeve optional) (AS=0" to 1") 1 or 2 Hour CFS-SILGG
W-L-4011WL4011m.pdf Aluminum Cable Tray (24" x 6") (AS=0" to 4") 1 or 2-hr FS 657
CFS-BL
W-L-4019WL4019d.pdf Spine Cable Tray 1 or 2- hr FS 657
CFS-BL
W-L-4034WL4034c.pdf Aluminum Cable Tray (24" x 4") (AS=0" to 5") 2-hour CP 620
CFS-BL
W-L-4038WL4038d.pdf Cable Tray 1 or 2-hr FS 657
CFS-BL
W-L-4048WL4048b.pdf Cable Rack in max. 24" x 36" opening 2-hour CP 675T
W-L-4049WL4049d.pdf Multiple Cable Racks (optional) in max. 24" x 36" opening 2-hour CP 675T
W-L-4050WL4050d.pdf Multiple Cable Racks (optional) in max. 36" x 48" opening 2-hour CP 675T
W-L-4060WL4060a.pdf Cable Tray 1 or 2-hr FS-ONE
W-L-4081WL4081b.pdf Cable tray through gypsum wall assembly (AS = 0" to 26") 1-hour or 2-hour CFS-BL
W-L-5025WL5025g.pdf Max. 10" steel pipe with max. 2" glass fiber insulation (Steel sleeve optional) 1 or 2-hr FS-ONE
W-L-5027WL5027f.pdf Max 2" steel, copper, conduit or EMT pipe with max. ¾" AB/PVC insulation within a steel sleeve 2-hour FS-ONE
W-L-5028WL5028m.pdf Max. 4" steel, max. 2" copper, conduit or EMT pipe with 1/2" to 1" AB/PVC insulation (AS = 0" to 1-1/2") 1 or 2-hr FS-ONE
W-L-5029WL5029p.pdf Max. 12" steel, cast iron or max. 6" copper 1", 1-1/2", or 2" glass fiber or max. 2" calcium silicate insulation 1 or 2-hr FS-ONE
W-L-5046WL5046h.pdf Max. 12" steel or max. 6" copper pipe with max. 3" FOAMGLAS insulation within a steel sleeve 1 or 2-hr FS-ONE
MW
W-L-5047WL5047j.pdf Max. 20" steel, max. 6" copper, conduit or max. 4" EMT pipe with max. 3" Paroc insulation (Steel sleeve optional) 1 or 2-hr FS-ONE
W-L-5073WL5073b.pdf Max. 6" steel, copper, conduit or EMT pipe with max. 1-1/2" glass fiber insulation in a sleeve 4-hour FS-ONE
MW
W-L-5096WL5096g.pdf Max. 12" steel or max. 6" copper pipe with max. 2" glass fiber insulation (steel sleeve optional) (AS = 0" to 1-7/8") 1-hr or 2-hr FS-ONE
W-L-5125WL5125d.pdf Max. 10" steel, cast iron or max. 4" copper pipe with max. 3" glass fiber insulation 2-hour CP 648-E
W-L-5126WL5126c.pdf Max. 10" steel pipe with max. 3" glass fiber insulation 2-hour CP 648-E
W-L-5143WL5143c.pdf Max. 1" copper with max. 3/4" thick AB/PVC (Shaft Wall) (sleeved) 1 or 2-hr FS-ONE
MW
W-L-5144WL5144c.pdf Max. 1" copper with max. 2" thick glass fiber (Shaft Wall) (sleeved) 1-hour FS-ONE
MW
W-L-5223WL5223a.pdf Max. 12" steel or 6" copper with Nom. 1-1/2" or 3" thick Foam Glass pipe insulation 1 or 2-hr FS-ONE
W-L-5224WL5224b.pdf Beverage Line Set - Max. 1/2" diameter PE or PEX tubing (Max qty = 12) with AB/PVC insulation 1 or 2-hr CP 648-E
FS-ONE
W-L-5225WL5225e.pdf Max. 4" PVC or CPVC plastic pipe with nom. 1-1/2" thick glass fiber pipe insulation (AS=0" to 1") 1 or 2-hr CP 648-E
FS-ONE
W-L-5240WL5240a.pdf Max. 8" steel, cast iron, 4" copper with 1" or 1-1/2" thick glass fiber pipe insulation (shaft wall) 2 Hr FS-ONE
W-L-5244WL5244c.pdf Max. 2" steel, cast iron, or copper w/ max. 2" glass fiber pipe insulation (shaft wall) 2 Hr CP 648-E
FS-ONE
MW
W-L-5257WL5257c.pdf Max. 4" steel, cast iron, or copper with 1-1/2"glass fiber insulation (AS = 0" to 7/8") 1 or 2-hr CP 601S
CP 606
FS-ONE
CFS-SILGG
W-L-5259WL5259c.pdf Max. 2" steel, cast iron or copper with 1-1/2" glass fiber (UL Classified U336 or U366 Wall) 2-Hour FS-ONE
W-L-5260WL5260b.pdf Max. 2" steel, cast iron or copper with 3/4" glass fiber (UL Classified U336 or U366 Wall) 2-Hour FS-ONE
W-L-5261WL5261a.pdf Max. 12" steel, cast iron or 6" copper with 2" foam glass insulation 2-hour FS-ONE
W-L-5263WL5263b.pdf Max. 4" steel, cast iron, max 2" copper with 3/4" AB/PVC pipe insulation (AS=0" to 7/8") 1 or 2-hr CP 606
FS-ONE
W-L-5274WL5274b.pdf Max. 2" steel, cast iron, or copper with 1-1/2" glass fiber pipe insulation (AS=0", cont. point of contact) 1 or 2-hr FS-ONE
W-L-5292WL5292a.pdf Max. 12" steel or cast iron pipe with max. 4" calcium silicate pipe insulation (AS = 0" to 1-1/4") 1 or 2 Hour FS-ONE
W-L-5293WL5293a.pdf Max. 1-1/2” CPVC (c) with 1” glass fiber 1 or 2-Hr FS-ONE
W-L-5294WL5294a.pdf Max. 2” CPVC (c) with 1” glass fiber or AB/PVC 1 or 2-Hr CP 648-E
FS-ONE
W-L-6017WL6017c.pdf Max. 12" x 4" Fiber Optic Cable Tray (ABS) 1 or 2-hr FS 657
CFS-BL
W-L-6019WL6019b.pdf Max. 11-1/4" x 4-1/4" Electrical Busway 1 or 2-hr FS-ONE
W-L-7017WL7017d.pdf Max. 6" diameter sheet metal duct w/o damper 1-hour FS-ONE
W-L-7018WL7018b.pdf Max. 6" diameter sheet metal duct with max. 1" thick glass fiber insulation (w/o damper) 2-hour FS-ONE
W-L-7040WL7040h.pdf Max. 48" x 24" sheet metal duct w/o damper 1 or 2-hr CP 601S
CP 606
FS-ONE
W-L-7042WL7042d.pdf Max. 20" spiral wound duct w/o damper, or 12" sheet metal duct 1 or 2-hr CP 601S
CP 606
FS-ONE
W-L-7059WL7059a.pdf Max. 24" x 12" sheet metal duct w/o damper with max. 1 ½" thickness foil scrim glass fiber duct insulation 1 or 2-hr FS-ONE
W-L-7068WL7068b.pdf Max. 6" sheet metal duct w/o damper (Shaft Wall) (sleeved) 1 or 2-hr FS-ONE
W-L-7069WL7069b.pdf Max. 7" x 7" sheet metal duct w/o damper (No angles) (Shaft Wall ) (sleeved) 1 or 2-hr FS-ONE
W-L-7096WL7096a.pdf Max. 13" x 12" sheet metal duct w/o damper (no angles) 1-hour FS-ONE
W-L-7121WL7121a.pdf Max. 30" x 24" air or grease duct with 1-1/2" thick Firemaster ® Fast Wrap manufactured by Thermal Ceramics 1 or 2 Hr FS-ONE
W-L-7124WL7124c.pdf Max. 32" Metal Fab Grease Duct (AS varies) 1 or 2-hr FS-ONE
W-L-7130WL7130a.pdf Mechanical support mechanisms (strut, steel cable, steel rod, steel angle) 1 or 2-hr CP 606
FS-ONE
W-L-7143WL7143c.pdf Max. 24" x 24" sheet metal duct w/o damper (no angles) (AS = 1/2" to 1")(In 2 Hour walls, AS = Min 0") 1 or 2-hr CP 606
W-L-7151WL7151d.pdf Max. 60" x 36" sheet metal duct (w/o damper) with max. 2" thick glass fiber duct insulation (angles fastened through insulation) (AS=1/4" to 1-1/4") 1 or 2-hr FS-ONE
W-L-7153WL7153a.pdf Max. 20" spiral wound duct or 12" sheet metal duct (w/o damper) with 1-1/2" glass fiber duct insulation (AS=1/4" to 1") 1 or 2-hr FS-ONE
W-L-7154WL7154b.pdf Mechanical Support Member (steel strut, steel angle, steel channel) (shaft wall) (membrane penetration) (AS=0" to 7/8") 1 or 2-hr FS-ONE
W-L-7155WL7155d.pdf Max. 100" x 100" sheet metal duct (w/o damper) (AS = 0" to 2") 1 or 2-hr CP 606
FS-ONE
CFS-SILGG
W-L-7156WL7156c.pdf Max. 100" x 100" sheet metal duct (w/o damper) with 1-1/2" or 2" thick glass fiber duct insulation (insulation split for angles) (AS=1/2" to 2") 1 or 2-hr FS-ONE
MW
W-L-7157WL7157a.pdf Max. 24" x 24" steel greas duct w/ 1-1/2" duct wrap manufactured by Unifrax 1 or 2-hr FS-ONE
W-L-7158WL7158a.pdf Max. 24" x 12" steel air or grease duct w/ 1-1/2" duct wrap manufactured by Unifrax 1 or 2-hr FS-ONE
W-L-7159WL7159a.pdf Max. 10" x 10" sheet metal duct (w/o damper) (AS=1/4" to 1") (no angles) 1-hour CP 606
W-L-7188WL7188a.pdf Max. W14 x 90 Steel I-beam service support (AS=1/2" to 3") 1 or 2-hr FS-ONE
MW
W-L-7198WL7198a.pdf Max. 4” sheet metal duct (30 Ga) 2-Hour FS-ONE
W-L-7213WL7213a.pdf Max. 48" x 24" sheet metal duct w/o damper (AS = 0" to 2") 1 or 2 Hour CFS-SILGG
W-L-7214WL7214a.pdf Max. 20" spiral wound duct w/o damper, or 12" sheet metal duct (AS = 0" to 1-1/2") 1 or 2 Hour CFS-SILGG
W-L-8004WL8004n.pdf Max. 2" steel or copper, EMT and cables 2-hour FS-ONE
MW
W-L-8013WL8013h.pdf Insulated or non-insulated steel, copper, conduit or EMT pipes, plastic pipe, cable tray or cables (single or bundled) 1 or 2-hr FS 657
CFS-BL
W-L-8014WL8014g.pdf Insulated or non-insulated steel, cast iron, copper, conduit or EMT pipes, plastic pipe, cable tray or cables (single or bundled) 1, 2, 3 or 4-hour FS 657
CFS-BL
W-L-8015WL8015a.pdf Multiple penetrants through gypsum wall assembly (combination of max 12" steel, max 6" copper, max 6" steel conduit, max 4" EMT) 1, 2, 3, or 4-hour CFS-BL
W-L-8019WL8019c.pdf Insulated or non-insulated steel, cast iron, copper, conduit or EMT pipes, flexible metal conduit or cables (single or bundled) 2-hour CP 620
W-L-8023WL8023c.pdf Max. 6" steel tube (16 Ga) and cables (Translogic) 1 or 2-hr FS-ONE
W-L-8035WL8035c.pdf Fiber Optic cable tray (ABS), Cable Bundle, Max. 2" Fiber Optic Raceway (PVC) (AS varies) 1 or 2-hr FS 657
CFS-BL
W-L-8047WL8047c.pdf HVAC Line Set (AS varies) 2-hour FS-ONE
W-L-8058WL8058c.pdf Insulated or non-insulated steel, copper, conduit or EMT, cable bundle 1 or 2-hr FS 657
CFS-BL
W-L-8059WL8059a.pdf Multiple steel pipe, steel conduit, EMT and/or cable bundle 1 or 2-hr CP 675T
FS-ONE
W-L-8065WL8065c.pdf Insulated or non-insulated steel or copper, nonmetallic pipes, and cables (AS varies) 1 or 2-hr FS-ONE
MW
W-L-8071WL8071b.pdf Multiple 2" steel, steel conduit,flexible steel gas linr, or EMT, max. 2" ENT, and cables 1 or 2-hr FS-ONE
W-L-8079WL8079c.pdf Insulated or non-insulated metallic, non metallic pipes, and cable bundle (AS varies) (unframed opening) 1 or 2-hr FS-ONE
W-L-8081WL8081a.pdf Multiple HVAC Line Sete (max qty 3) bundled together (AS=0" to 1-1/2") 1 or 2-hr CP 648-E
FS-ONE
W-L-8082WL8082a.pdf Misc. bundle consisting of cables, metal pipe, ENT (AS=0" to 1") 1 or 2-hr CP 648-E
W-L-8085WL8085a.pdf HVAC Line Set through CP 653 Speed Sleeve 1 or 2-hr CP 606
CP 653
FS-ONE
W-L-8086WL8086a.pdf Cable bundle and metallic pipe through CP 653 Speed Sleeve 1 or 2-hr CP 606
CP 653
FS-ONE
W-L-8087WL8087b.pdf Insulated or non-insulated metallic, non-metallic, cable bundles (AS varies) 1 or 2-hr CFS-BL
W-L-8093WL8093b.pdf Multiple penetrating items through gypsum wall assembly (various cable and pipe sizes) 1, 2, 3, or 4-hour CFS-BL
W-L-8094WL8094a.pdf Multiple penetrating items through gypsum wall assembly (various cable and cable bundle sizes) 1-hour or 2-hour CFS-BL
W-L-8095WL8095b.pdf Multiple penetrations through gypsum wall assembly (various pipe, conduit, and tubing sizes) 1-hour or 2-hour CFS-BL
W-L-8098WL8098a.pdf Metal pipes, insulated pipes, cable bundles through Gypsum Shaft Wall (No max annular space) 1 or 2 Hour CFS-BL